Page County Unincorporated, Virginia · General provision
Data Center
Dimensional standards
Uses
Conditional / special use1
Extracted standards
5 individual requirements pulled out of this section’s prose, each with the sentence it came from.
Fencing & walls
- Minimum fence heightMaximum heightThe tallest a building may be, given in feet, in storeys, or both — whichever binds first.6 ft
The site shall be enclosed by a fence at least six feet in height with a locked gate at all access points.
Landscaping & trees
- Minimum vegetated buffer width50 ft
A vegetated buffer of at least 50 feet in width shall be maintained along all property lines.
Lighting
- Full cutoff lighting required
All exterior lighting shall be full cutoff fixtures directed downward to minimize glare onto adjacent properties and roadways.
Other
- Backup generator testing
Backup generators shall be equipped with noise suppression devices and shall be tested only during daylight hours, except in the case of an emergency.
- Construction hours
Hours of operation for construction activities shall be limited to 7:00 a.m. to 7:00 p.m., Monday through Saturday.
From the ordinance
The maximum height of any data center building shall be 60 feet. The site shall be enclosed by a fence at least six feet in height with a locked gate at all access points. A vegetated buffer of at least 50 feet in width shall be maintained along all property lines.