King George County Unincorporated, Virginia · General provision

Section 7-6-5

Dimensional standards

Uses

Permitted by right1

Prohibited1

Extracted standards

8 individual requirements pulled out of this section’s prose, each with the sentence it came from.

Design

  • Principal façade requirements

    Principal façade requirements apply to all building facades that face adjacent existing or planned public roads or that face an adjacent property with existing residential development... Principal facades must have differentiated surfaces, consistent design and fenestration to create visual interest and consistency with community character.

Height

Other

  • Generator testing hours

    Generator testing shall be limited to weekdays between 8:00 a.m. and 5:00 p.m.

  • Ground mounted mechanical equipment is prohibited in front yards.

  • Mechanical infrastructure screening

    Power generators, water cooling systems, storage facilities and any other mechanical infrastructure necessary for the operations of the data center shall be within an enclosed structure screened as not to be visible from any adjacent street, use, or building.

  • Solid screening walls with engineered sound barriers

    Solid screening walls must be constructed with engineered sound barriers and design, materials, and treatment compatible with those used on the nearest Principal façade of a building but may include perforated surfaces as needed for ventilation of mechanical equipment.

  • Transitional buffers allowed

    Transitional buffers allowed include Type C and Alternative Buffer Berms as supplied in Article VIII, Community Design Standards.

  • Utility company approval required

    No data center shall be built until evidence has been given as part of the application that the owner has been approved by the utility company.

From the ordinance

Due to the high-water demand, data centers shall be connected to public or community water system if a water-based cooling system is utilized. ... The allowed Floor Area Ratio maximum is 0.6.
Section 7-6-5