Section 7-6-5
Dimensional standards
Extracted standards
6 individual requirements pulled out of this section’s prose, each with the sentence it came from.
Design
- Principal façade requirements
Principal façade requirements apply to all building facades that face adjacent existing or planned public roads or that face an adjacent property with existing residential development...
Noise
- Generator testing hours
Generator testing shall be limited to weekdays between 8:00 a.m. and 5:00 p.m.
Other
- Ground mounted mechanical equipment prohibitedProhibitedNot allowed in the district at all, short of rezoning or a variance. in front yards
Ground mounted mechanical equipment is prohibited in front yards.
- Mechanical equipment screening
Power generators, water cooling systems, storage facilities and any other mechanical infrastructure... shall be within an enclosed structure screened as not to be visible from any adjacent street, use, or building.
- Transitional buffers allowed
Transitional buffers allowed include Type C and Alternative Buffer Berms as supplied in Article VIII, Community Design Standards.
- Public/community water connection required for water-based cooling
Data centers shall be connected to public or community water system if a water-based cooling system is utilized.
From the ordinance
Due to the high-water demand, data centers shall be connected to public or community water system if a water-based cooling system is utilized.