King George County Unincorporated, Virginia · General provision

Section 7-6-1

Extracted standards

7 individual requirements pulled out of this section’s prose, each with the sentence it came from.

Other

  • Buffer from vegetation20 ft

    Buffer the facility from the surrounding areas by siting toward the interior of the lot, at least 20 feet away from vegetation

  • Fire suppression system required

    Each Battery Energy Storage Facility shall install and maintain an automatic fire alarm/detection system, fire suppression system, and other extinguishing technology built in based on specific hazards.

  • Full screening required

    Facilities shall be fully screened on all sides from view, except from an adjacent parcel on the same side of the road with an electric substation or a parcel that is zoned industrial.

  • All security fencing shall be a minimum of 8 ft. in height and topped with razor/barbed wire, as appropriate.

Setback

Signage

  • NFPA 704 placards required

    NFPA 704 placards shall be placed on building entrances along with emergency contact information.

From the ordinance

Be located at least 200 feet from any residential district, planned development district, or dwelling; Be located at least 100 feet from agricultural, commercial, or industrial districts, except for an adjacent parcel with an electric substation to which the Battery Energy Storage Facility will connect.
Section 7-6-1