Claremont, Virginia · General provision

Sec. 3-1516(A)6

Coastal High HazardAll Claremont districts0

Dimensional standards

Servicing

Geographic extent
Areas identified as VE or V Zones on the FIRM (coastal high hazard areas)

Extracted standards

9 individual requirements pulled out of this section’s prose, each with the sentence it came from.

Design

  • Engineer/architect certification

    A registered professional engineer or architect shall develop or review the structural design, specifications and plans for the construction, and shall certify that the design and methods of construction to be used are in accordance with accepted standards of practice.

Other

  • Anchoring to resist flotation

    The pile or column foundation and structure attached thereto is anchored to resist flotation, collapse, and lateral movement due to the effects of wind and water loads acting simultaneously.

  • Enclosed space use restrictions

    The enclosed space below the lowest floor shall be used solely for parking of vehicles, building access, or storage. Such space shall not be partitioned into multiple rooms, temperature-controlled, or used for human habitation. The enclosed space shall be less than 300 square feet.

  • The use of fill for structural support of buildings is prohibited.

  • Landward of mean high tide

    All new construction shall be located landward of the reach of mean high tide.

  • Lowest horizontal structural member elevation above BFE1.5 ft

    The bottom of the lowest horizontal structural member of the lowest floor is elevated to or above the base flood level plus 18 inches if the lowest horizontal structural member is parallel to the direction of wave approach.

  • Lowest horizontal structural member elevation above BFE (perpendicular)1 ft

    Elevated at least one foot above the base flood level if the lowest horizontal structural member is perpendicular to the direction of wave approach.

  • The man-made alteration of sand dunes, which would increase potential flood damage, is prohibited.

  • Space below lowest floor

    The space below the lowest floor shall be either free of obstruction or constructed with non-supporting breakaway walls, open wood-lattice work, or insect screening intended to collapse under wind and water loads without causing structural damage.

From the ordinance

All new construction and substantial improvements in Zones V and VE shall be elevated on pilings or columns so that the bottom of the lowest horizontal structural member of the lowest floor is elevated to or above the base flood level plus 18 inches if the lowest horizontal structural member is parallel to the direction of wave approach or elevated at least one foot above the base flood level if perpendicular.
Sec. 3-1516(A)6