Claremont, Virginia · General provision

Sec. 4-609

Dimensional standards

Uses

Extracted standards

9 individual requirements pulled out of this section’s prose, each with the sentence it came from.

Lighting

  • Motion-sensor lighting required

    all lighting shall be exclusively motion-sensor activated. All lighting must be in compliance with the International Dark-Sky Association's (IDA) guidelines

Noise

  • Maximum noise at occupied structure in AR55 dBA

    shall not exceed 55 dBA at the outer wall of any occupied structure on an adjacent parcel in the AR district in existence at the time the project receives its conditional use permit.

  • Maximum noise at property line65 dBA

    The average noise generated from the battery energy storage systems, components, and associated ancillary equipment at any time shall not exceed a noise level of 65 dBA as measured from the property line of an adjoining parcel

Other

Setback

Signage

From the ordinance

Battery energy storage systems shall comply with the following minimum setback requirements: In the A-R District: Be located at least 200 feet from all property lines, unless the adjacent parcel is zoned industrial, has an electric substation to which the battery energy storage system will connect and is located on the same side of the road, or is an adjacent parcel owned or leased by the battery energy storage system's owner or operator. Be located 500 feet from all residential and commercial structures. In the M-1 and M-2 District: Be located a minimum of at least 75 feet from all property lines and otherwise comply with all minimum height, bulk, setback, and yard requirements of the underlying district.
Sec. 4-609