Dendron, Virginia · General provision

Sec. 4-609

Dimensional standards

Uses

Conditional / special use1

Extracted standards

9 individual requirements pulled out of this section’s prose, each with the sentence it came from.

Fencing & walls

Landscaping & trees

  • Minimum vegetative buffer width100 ft

    Battery energy storage systems located in the A-R district shall be fully screened on all sides from ground-level view by a vegetative buffer of at least 100 feet located within the required setbacks...

Lighting

  • Motion-sensor lighting

    Lighting of any battery energy storage system shall be limited to that minimally required for safety and operational purposes and all lighting shall be exclusively motion-sensor activated. All lighting must be in compliance with the International Dark-Sky Association's (IDA) guidelines...

Noise

  • Maximum noise at occupied structure55 dBA

    and shall not exceed 55 dBA at the outer wall of any occupied structure on an adjacent parcel in the AR district in existence at the time the project receives its conditional use permit.

  • Maximum noise at property line65 dBA

    The average noise generated from the battery energy storage systems, components, and associated ancillary equipment at any time shall not exceed a noise level of 65 dBA as measured from the property line of an adjoining parcel...

Other

  • Decommissioning timeline6 months

    The decommission process shall occur within six months after the battery energy storage system permanently ceases operation.

  • Be located at least 200 feet from all property lines, unless the adjacent parcel is zoned industrial, has an electric substation to which the battery energy storage system will connect and is located on the same side of the road, or is an adjacent parcel owned or leased by the battery energy storage system's owner or operator.

  • Minimum setbackSetbackThe distance a building must be held back from a lot line. from residential and commercial structures500 ft

    Be located 500 feet from all residential and commercial structures.

Signage

From the ordinance

Battery energy storage systems shall comply with the following minimum setback requirements: In the A-R District: Be located at least 200 feet from all property lines... Be located 500 feet from all residential and commercial structures.
Sec. 4-609