Fencing & walls
- Battery energy storage fence heightMaximum heightThe tallest a building may be, given in feet, in storeys, or both — whichever binds first.8 ft
Battery energy storage systems shall be enclosed by a security fence at least eight feet in height or other greater height as required by applicable codes or design requirements of the operating entity.
Height
- Battery energy storage maximum heightMaximum heightThe tallest a building may be, given in feet, in storeys, or both — whichever binds first.30 ft
Battery energy storage systems shall not exceed a height of 30 feet, except for structures associated with interconnection to the electrical grid.
Noise
- Battery energy storage maximum noise level65 dBA
The average noise generated from the battery energy storage systems, components, and associated ancillary equipment at any time shall not exceed a noise level of 65 dBA as measured from the property line of an adjoining parcel and shall not exceed 55 dBA at the outer wall of any occupied structure on an adjacent parcel in the AR district in existence at the time the project receives its conditional use permit.
From the ordinance
Battery energy storage systems shall be enclosed by a security fence at least eight feet in height... Battery energy storage systems shall not exceed a height of 30 feet... The average noise generated from the battery energy storage systems... shall not exceed a noise level of 65 dBA...