Riverside, California · General provision
Chapter 19.480 (Private Fueling Systems with Above-Ground Tanks)
Dimensional standards
Extracted standards
3 individual requirements pulled out of this section’s prose, each with the sentence it came from.
Other
- Maximum cumulative tank capacity12,000 gallons
The fueling system shall be limited to two tanks, with a maximum cumulative capacity of 12,000 gallons.
- Full screening required
The tanks shall be fully screened from adjoining streets and neighboring properties.
Setback
- Minimum distance from residential structures300 ft
Above-ground fuel tanks of 1,000 gallons or more shall be located a minimum distance of 300 feet from any residential structure or residentially zoned property.
From the ordinance
The fueling system shall not exceed ten feet in height.