Marin County Unincorporated, California · General provision
22.42.025.J
Dimensional standards
Height & bulk
Servicing
- Geographic extent
- All zoning districts
Extracted standards
3 individual requirements pulled out of this section’s prose, each with the sentence it came from.
Other
- Maximum generator heightMaximum heightThe tallest a building may be, given in feet, in storeys, or both — whichever binds first.4 ft
do not exceed a height of four feet above grade
- Minimum generator front setbackSetbackThe distance a building must be held back from a lot line.25 ft
minimum front yard setback of 25 feet
- Minimum generator side and rear setbackSetbackThe distance a building must be held back from a lot line.10 ft
minimum side and rear yard setbacks of 10 feet
From the ordinance
The installation of power generators that do not exceed a height of four feet above grade and have a minimum front yard setback of 25 feet and minimum side and rear yard setbacks of 10 feet, provided they are not developed on a property with multiple primary units.