Loudoun County Unincorporated, Virginia · General provision
Section 4.07.02.C
Dimensional standards
Servicing
- Geographic extent
- Applies to Site-Specific Energy Storage Facilities
Extracted standards
4 individual requirements pulled out of this section’s prose, each with the sentence it came from.
Other
- Maximum container size900 sqftsq ftSquare feet. An acre is 43,560 sq ft; a typical suburban lot is 7,000–10,000.
Containers housing energy storage equipment are limited to 900 square feet in size.
- Maximum gross floor area for data centers30 pct
For data centers, site-specific Energy Storage Facilities must not exceed 30% of the gross floor area of the use
- Placement in commercial/industrial districts
The Energy Storage Facility must be located within the principal building or within a permitted accessory building. Alternately, the Energy Storage Facility may be located on the roof of the principal building when fully screened from public view.
- Placement in residential/agriculturalAgricultureRaising crops or livestock, generally including the structures that serve them. districts
The Energy Storage Facility must be located within or attached to the principal building or a permitted accessory building.
From the ordinance
A site-specific Energy Storage Facility must serve the on-site needs of the property on which it is located. For data centers, site-specific Energy Storage Facilities must not exceed 30% of the gross floor area of the use. The Energy Storage Facility must be located within or attached to the principal building or a permitted accessory building. Containers housing energy storage equipment are limited to 900 square feet in size.