Section 4.07.02.C
Dimensional standards
Servicing
- Geographic extent
- Applies to Site-Specific (On-Site Accessory UseAccessory useA secondary activity customarily incidental to the main use of the lot — a garage, a home office.) Energy Storage Facilities.
Extracted standards
5 individual requirements pulled out of this section’s prose, each with the sentence it came from.
Other
- Placement in commercial/industrial districts
The Energy Storage Facility must be located within the principal building or within a permitted accessory building. Alternately, the Energy Storage Facility may be located on the roof of the principal building when fully screened from public view.
- Data center limitation30 pct
For data centers, site-specific Energy Storage Facilities must not exceed 30% of the gross floor area of the use; otherwise, the use is subject to the requirements for utility scale Energy Storage Facilities in Section B.
- Maximum container size900 sqftsq ftSquare feet. An acre is 43,560 sq ft; a typical suburban lot is 7,000–10,000.
Containers housing energy storage equipment are limited to 900 square feet in size.
- Placement in residential/agriculturalAgricultureRaising crops or livestock, generally including the structures that serve them. districts
The Energy Storage Facility must be located within or attached to the principal building or a permitted accessory building.
- HeightMaximum heightThe tallest a building may be, given in feet, in storeys, or both — whichever binds first. and setbacksSetbackThe distance a building must be held back from a lot line. subject to underlying districtZoning districtA mapped area with one set of rules, identified by a code like R-1 or B-2.
The Energy Storage Facility is subject to the requirements of the underlying Zoning District.
From the ordinance
A site-specific Energy Storage Facility must serve the on-site needs of the property on which it is located.