King William County Unincorporated, Virginia · General provision

Sec. 86-386, 86-387, 86-388

Uses

Conditional / special use1

  • Tier 2 battery energy storage system (in A-C and I districts)

Extracted standards

6 individual requirements pulled out of this section’s prose, each with the sentence it came from.

Lighting

  • Lighting limited to safety and operational

    Lighting of the battery energy storage systems shall be limited to that minimally required for safety and operational purposes.

Noise

  • Noise regulated by county code

    Noise shall be regulated by Article II of the King William County Code.

Other

  • Tier 1 maximum capacity600 kWh

    Tier 1 battery energy storage systems have an aggregate energy capacity less than or equal to 600 kWh for onsite use only.

  • Tier 2 minimum capacity600 kWh

    Tier 2 battery energy storage systems have an aggregate energy capacity greater than 600 kWh.

  • Underground utilities required

    All on-site utility lines shall be placed underground to the extent feasible...

Signage

From the ordinance

Tier 1 battery energy storage systems shall be permitted in all zoning districts, as accessory to a permitted use. Tier 2 battery energy storage systems are permitted through the issuance of a conditional use permit...
Sec. 86-386, 86-387, 86-388