King William County Unincorporated, Virginia · General provision
Sec. 86-386, 86-387, 86-388
Uses
Permitted by right1
Conditional / special use1
- Tier 2 battery energy storage system (in A-C and I districts)
Extracted standards
6 individual requirements pulled out of this section’s prose, each with the sentence it came from.
Lighting
- Lighting limited to safety and operational
Lighting of the battery energy storage systems shall be limited to that minimally required for safety and operational purposes.
Noise
- Noise regulated by county code
Noise shall be regulated by Article II of the King William County Code.
Other
- Tier 1 maximum capacity600 kWh
Tier 1 battery energy storage systems have an aggregate energy capacity less than or equal to 600 kWh for onsite use only.
- Tier 2 minimum capacity600 kWh
Tier 2 battery energy storage systems have an aggregate energy capacity greater than 600 kWh.
- Underground utilities required
All on-site utility lines shall be placed underground to the extent feasible...
Signage
- Maximum sign size4 sqftsq ftSquare feet. An acre is 43,560 sq ft; a typical suburban lot is 7,000–10,000.
The sign shall not exceed four square feet in size.
From the ordinance
Tier 1 battery energy storage systems shall be permitted in all zoning districts, as accessory to a permitted use. Tier 2 battery energy storage systems are permitted through the issuance of a conditional use permit...