Blackstone, Virginia · General provision

Sec. 30-53

Extracted standards

6 individual requirements pulled out of this section’s prose, each with the sentence it came from.

Other

  • Key box maintenance

    The operator of the building shall immediately notify the fire code official if the location of the key box changes. The operator of the building is responsible for the maintenance of the key box to ensure it functions properly.

  • not to exceed three to five feet off the ground

  • Knox Box required for restricted access buildings

    Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a Knox Box be installed in an approved location not to exceed three to five feet off the ground.

  • Knox Box UL 1037 listing

    The Knox Box shall be of an approved type listed in accordance with UL 1037.

  • Knox lock on gates and valves

    An approved Knox lock shall be installed on gates, sprinkler system post-indicator valves, or similar barriers when required by the fire code official.

  • Standardized fire service elevator keys

    All buildings with elevators equipped with Phase I emergency recall or Phase II emergency in-car operation, or buildings equipped with fire service access or occupant evacuation elevators shall be equipped to operate with a standardized fire service key approved by the fire code official.

From the ordinance

The Town of Blackstone hereby adopts the following provision of the 2009 Virginia Statewide Fire Prevention Code. This section shall apply to newly constructed commercial buildings or structures, newly constructed industrial buildings or structures and to newly constructed multifamily residential structures that have restricted access through locked doors and have a common corridor for access to the living units. ... Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a Knox Box be installed in an approved location not to exceed three to five feet off the ground.
Sec. 30-53