Richmond, California · General provision

15.04.710.120

Extracted standards

5 individual requirements pulled out of this section’s prose, each with the sentence it came from.

Lighting

  • Maximum spacing of pull boxes on straight runs200 ft

    Either a pull box or a street lighting standard with a handhole shall be placed at all sharp bends in the conduit or every 200 feet on straight runs of conduit.

  • Minimum illumination for collector streets0.6 foot-candle

    0.6 foot-candle for collector streets

  • Minimum illumination for major arterials1 foot-candle

    1.0 foot-candle for major arterials

  • Minimum illumination for minor streets0.4 foot-candle

    0.4 foot-candle for minor streets

  • Minimum illumination for paths0.2 foot-candle

    0.2 foot-candle for paths

From the ordinance

The minimum average illumination ... shall be 1.0 foot-candle for major arterials, 0.6 foot-candle for collector streets, 0.4 foot-candle for minor streets, and 0.2 foot-candle for paths.
15.04.710.120